250 kVA Generator for Sale and Rent in Saudi Arabia
A 250 kVA generator gives about 200 kW of real power and draws about 361 A per phase. Before comparing prices, make sure this size really matches your loads: too small and it trips, too big and it burns fuel and wears out.

Where is a 250 kVA generator used?
Medium factories
Production lines, air compressors and plant lighting.
Towers and compounds
Lifts, water pumps and cooling for shared areas.
Large farms
Well pumps, irrigation and cooling.
Project sites
Cranes and site equipment before grid power arrives.
The numbers you need before buying
| Item | Approx. value |
|---|---|
| Real power | 200 kW |
| Current at 400 V | 361 A |
| Current at 380 V | 380 A |
| ATS panel | 400 A |
| 24,000 BTU split ACs | about 60 with staggered starting |
| Diesel at 75% load | 41 litres per hour |
| Diesel at full load | 50 litres per hour |
Values are approximate and change with the model and site temperature. Compare every size in the generator kVA to amps chart.
What many buyers miss at this size
Electronic loads
UPS units and motors on variable speed drives distort the current. They need a larger than usual alternator, or it runs hot and panels start to fault.
Generator room ventilation
A set this size throws off a lot of heat. A room without properly sized air openings raises the temperature around the set and cuts its output, a common cause of summer tripping.
Engines common at this size
| Brand | Engine family |
|---|---|
| Cummins | 6CTA8.3 |
| Perkins | 1506 |
| Volvo Penta | TAD7 |
The engine family changes with frequency and with standby or prime rating, so we confirm the exact model in the quote.
Models close to 250 kVA
250 kVA generator questions
How many amps is a 250 kVA generator?
About 361 A per phase at 400 V and 380 A at 380 V.
How many AC units can a 250 kVA generator run?
About 78 split units of 18,000 BTU or 60 of 24,000 BTU, with staggered starting and no other large loads.
How much diesel does a 250 kVA generator use?
About 41 litres per hour at 75% load and 50 litres at full load. Light loads use less fuel, but long runs at light load harm the engine.
Do you rent 250 kVA generators?
For large sizes we offer long term project rental depending on availability. At this size most clients buy with a maintenance contract.