Generator Terms Glossary
More than 30 terms you will meet in generator quotes and catalogues, with a short note on what each means and why it matters to your choice. Useful before reading any quote or comparing two models.

Terms
kVA ك.ف.أ
Apparent power, the figure generators are sold by. It covers real power plus the power motors and transformers use to build their magnetic field.
kW كيلوواط
Real power that does work. On generators kW is usually kVA times 0.8.
Power factor معامل القدرة
The ratio of kW to kVA. Generators are designed for 0.8, and loads below it need a larger set.
Standby rating القدرة الاحتياطية
The highest output for limited hours a year during outages only. Not for daily running.
Prime rating القدرة الرئيسية
Output the set can give for unlimited hours on a varying load. The reference for daily use.
Continuous rating القدرة المستمرة
Output at a constant load with no limit on hours, required by data centres and plants.
Alternator مولد التيار
The part that turns engine rotation into electricity. Its size and insulation class decide how it copes with hard loads.
AVR منظم الجهد
A circuit that holds output voltage as the load changes. A precise one protects sensitive equipment.
Governor الحاكم
Controls engine speed and so frequency. Electronic governors respond faster than mechanical ones.
ATS لوحة التحويل الأوتوماتيكي
Moves the load from mains to the generator on outage and back when mains returns, without anyone on site.
AMF التشغيل عند الانقطاع
A controller function that starts the set automatically when mains fails.
Synchronising panel لوحة التزامن
Runs several sets in parallel and shares the load between them.
Load bank جهاز تحميل
An artificial load used to test a set up to full output without running the building.
Insulation class فئة العزل
The highest temperature the alternator windings can take. Class H is the highest in common use.
IP rating درجة الحماية
How well the alternator is protected from dust and water. IP23 is usual inside a canopy.
Silent canopy كاتم الصوت
A sound proof enclosure. Its level is measured in dB at 7 metres and should be a number in the quote.
Base tank خزان القاعدة
A diesel tank built into the base frame, setting the hours before refuelling.
Day tank الخزان اليومي
A small tank near the set fed from a bulk tank, used on larger sites.
Water separator فاصل الماء
A filter that removes water from diesel before the engine, drained regularly.
Jacket water heater سخان المحرك
Keeps coolant warm on a standby set so it starts and takes load quickly.
Anti condensation heater سخان منع التكثيف
Stops moisture condensing inside a standby alternator. Essential in coastal cities.
DOL start الإقلاع المباشر
Starting a motor straight on line. It draws five to seven times its running current.
Star delta ستار دلتا
A starting method that cuts starting current to about a third.
Soft starter البادئ الناعم
Ramps motor voltage on start and reduces the set size needed for pumps and compressors.
VFD مغير السرعة
Controls motor speed and saves energy but creates distortion that needs a larger alternator.
THD التشوه التوافقي
Distortion of the current waveform caused by UPS, VFDs and modern lighting. It heats the alternator.
Block load acceptance قبول الحمل
How much load the set can take at once without a deep dip in voltage and frequency.
Wet stacking تراكم الكربون
Builds up when a set runs long on a very low load, leaving unburnt fuel in the exhaust.
N+1 التكرار
One more set than needed, so the full load stays on if one set stops.
ISO 8528
The international standard for generator ratings and performance, including standby, prime and continuous.
Reference conditions الظروف القياسية
Nameplate output is set at 25 C and normal air pressure. Above that, real output falls.
Commissioning اختبار التشغيل
Running the set on site on real load or a load bank and recording readings before acceptance.