Why Two Generators of the Same Size Differ

Two sets both rated 500 kVA: one trips when the AC starts, the other copes. The nameplate does not tell the whole story, and these are the parts the catalogue does not print large.

A row of containerised generators on site

What makes the difference

Engine displacement

A larger engine runs at a lower share of its capacity for the same output, so it handles sudden loads and lasts longer.

Alternator size

An alternator larger than the engine copes with motor starts and UPS loads without voltage dips or heat.

Load acceptance

Some sets take half their load at once, others far less. This shows in ISO 8528 data, not the brochure.

Output in heat

Ratings assume 25 C. A radiator built for 50 C keeps output in summer while a standard one trips.

Governor and AVR

Electronic ones restore speed and voltage quickly after any load change, and sensitive equipment notices.

Fuel use

A few litres an hour becomes thousands of litres a year on a set that runs daily.

What to ask for before buying

  • The full data sheet, not the brochure page.
  • Engine displacement in litres and model.
  • Alternator model and rating, separate from the engine.
  • Fuel use at 75 and 100 percent load.
  • The ambient temperature the radiator is designed for.

Read also Cummins or Perkins and how to compare two quotes.